Should Buck-Boost transformers be used to develop 3-phase 4 wire Wye circuits from 3-phase 3 wire Delta circuits?

No – a three-phase “Wye” buck-boost transformer connection should be used only on a 4-wire source of supply. A delta to Wye connection does not provide adequate current capacity to accommodate unbalanced currents fl owing in the neutral wire of the 4-wire circuit.